Error
Error name
Error details and cause
code
3005H
Boot function
• When the boot function is executed,
execution error
the security key registered in the CPU
module (or cassette) does not match
the one that locks the boot source
program.
• When the boot function is executed,
the security key is not registered in
the CPU module (or cassette) even
though the boot source program is
locked with the security key.
• The program files and FB files that
are written to an SD memory card
using the memory card operation of
the engineering tool is set to boot
targets.
300CH
Execution error
• The firmware update cannot be
of functions
executed because the firmware
using memory
update file is not stored in the memory
card
card.
• The automatic restoration function
with the SD CARD OFF button cannot
be executed because the system file
for the function is not stored in the
memory card.
3010H
Data restoration
• The model of the restoration target
function
CPU module differs from the model of
execution error
the backup source CPU module.
3011H
Data restoration
• Reading of backup data from an SD
function
memory card completed with an error.
execution error
3012H
Data restoration
• Writing of backup data to the CPU
function
built-in memory completed with an
execution error
error.
3013H
Data restoration
• The system file does not exist in the
function
backup data to be restored.
execution error
• File(s) in the system file information
does not exist in the folder of the
backed up data.
3014H
Data restoration
• Data was restored to the CPU module
function
where the same data with a file
execution error
password has already been stored.
Stop/
Action
continue
Stop
• Check and correct the security key
setting.
• Delete the boot settings from the
memory card parameter.
• Write the boot target program files
and FB files to the SD memory
card on the CPU module using the
online data operation of the
engineering tool.
Stop
• If the automatic restoration
function with the SD CARD OFF
button cannot be executed, take
either of the following actions.
(1) Check that the system file for
automatic restoration with the SD
CARD OFF button is stored.
(2) Turn on bit 2 of SD955
(Automatic restoration with the
SD CARD OFF button) before
backing up the data.
Stop
• Execute the data restoration
function to the CPU module
whose model is the same as that
of the backup source CPU
module.
• Turn off bit 0 of SD955 to disable
the automatic data restoration
function.
Stop
• Replace an SD memory card, and
execute the function again.
• The backup data may have been
corrupted. Execute the data
restoration function using another
backup data.
• Turn off bit 0 of SD955 to disable
the automatic data restoration
function.
Stop
• The possible cause is a hardware
failure of the restoration target
CPU module. Execute the data
restoration function to another
CPU module.
Stop
• The backup data may have been
corrupted. Execute the data
restoration function using another
backup data.
• Turn off bit 0 of SD955 to disable
the automatic data restoration
function.
Stop
• Delete file passwords, and
execute the CPU module data
backup/restoration function.
• Turn off bit 0 of SD955 to disable
the automatic data restoration
function.
Detailed
Diagnostic
information
timing
Drive/file
At power-on, at
information
RESET
At power-on, at
RESET
CPU module
At power-on, at
data backup/
RESET
restoration
folder
information
CPU module
At power-on, at
data backup/
RESET
restoration
folder
information,
drive/file
information
CPU module
At power-on, at
data backup/
RESET
restoration
folder
information,
drive/file
information
CPU module
At power-on, at
data backup/
RESET
restoration
folder
information
CPU module
At power-on, at
data backup/
RESET
restoration
folder
information