3 SPECIFICATIONS

3.2.12 Control output setting at CPU stop error occurrence

3 - 22
Downloaded from
ManualsNet.com
(3) The Q64TC allows four different alerts (alert 1 to 4) to be selected and used from
among the alerts, wait alert and re-wait alert.
Set the alerts mode used as alerts 1 to 4 at the following buffer memory
addresses:
Mode setting item
Alert 1
Alert 2
Alert 3
Alert 4
(4) Set the alert set value, alert dead band value and alert delay count at the following
buffer memory addresses:
Channel No.
1
2
3
4
(1) You can set the Q64TC control output (HOLD/CLEAR) to be provided when the
programmable controller CPU has generated a stop error.
(2) To make this setting, use the intelligent function module switch setting on GX
Developer.
• CLEAR : Stops the PID control, temperature judgement and alert judgement
functions and turns off external outputs.
• HOLD
: Holds the control status prior to a programmable controller CPU stop.
For example, when PID control was exercised before a programmable
controller CPU stop, PID control is continued if the programmable
controller CPU stops.
Refer to Section 4.5 for details of the setting method.
search engine
CH1
CH2
C0
D0
H
H
C1
D1
H
H
C2
D2
H
H
C3
D3
H
H
Buffer memory address
Alert set value
Alert dead band value
26
to 29
H
H
46
to 49
H
H
66
to 69
H
H
86
to 89
H
H
MELSEC-Q
CH3
CH4
E0
F0
H
E1
F1
H
E2
F2
H
E3
F3
H
Alert delay count
A4
A5
H
H
3 - 22
H
H
H
H