Monitored Data - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
9.10.9
REX640
Technical Manual

Monitored data

Table 1426:
OL5ATCC Monitored data
Name
Type
U_MEAS
FLOAT32
ANGL_UA_IA
FLOAT32
TIMER_STS
Enum
OPR_MODE_STS
Enum
U_CTL
FLOAT32
UD_CTL
FLOAT32
I_CIR
FLOAT32
LDC
FLOAT32
BLK_STATUS
INT32
ALARM_REAS
Enum
Table continues on next page
Values (Range)
Unit
0.00...5.00
xUn
-180...180
deg
0=Timer off
1=Lower timer1
on
2=Raise timer1
on
3=Lower timer2
on
4=Raise timer2
on
5=Fast lower T
on
0=Not in use
1=Manual
2=Auto single
3=Parallel
manual
4=Auto master
5=Auto follower
6=MCC
7=NRP
0.000...3.000
xUn
-2.000...2.000
xUn
-10.00...10.00
xIn
-2.00...2.00
xUn
0...127
0=No alarm
1=Cmd error
2=TCO error
3=Cmd + TCO
err
4=Pump error
5=Pump + cmd
err
6=Pump + TCO
err
7=Pmp+TCO
+cmd err
Section 9
Control functions
Description
Phase-to-phase voltage,
average filtered
Measured angle value
between phase A voltage
and current
Timer T1, T2 or fast lower
timer active
The acting operation
mode of the function
block
Control voltage, Up,
target voltage level
Voltage difference
between Measured
voltage - Control Voltage:
Um - Up
Calculated circulating
current - calculated in
operation modes NRP
and MCC
Calculated line drop
compensation
Bit-coded output showing
the blocking status for the
next operation
Status and reason for
alarm
1569