Chassis Clearances
6
7
8
Cisco Nexus 7010 Chassis Clearances
The Cisco Nexus 7010 chassis requires the following clearances (see
•
•
Cisco Nexus 7000 Series Hardware Installation and Reference Guide
A-32
Air intake from cold aisle for the supervisor,
fabric, and I/O modules
Air exhaust to hot aisle for the power supplies 15 Clearance required between the front of the
Air exhaust to hot aisle for the supervisor,
fabric, and I/O modules
Front clearance of 45.5 inches (115.6 cm) for both of the following:
Cabling area of 7.5 inches (19.1 cm) between the front of the chassis and the inside of the
–
cabinet or front of the rack
Maintenance area of 38 inches (96.5 cm) of cold-aisle passageway in front of the rack or cabinet
–
You might need to increase the maintenance area to accommodate a wide mechanical lift
Note
used to move the chassis to or from the rack.
Rear clearance of 35 inches (88.9 cm) for both of the following:
Airflow area of 5 inches (12.7 cm) inside of the cabinet or rack
–
Maintenance area of 30 inches (76.2 cm) of hot-aisle passageway behind the rack or cabinet
–
Appendix A
14 Chassis depth
chassis and the front of the cable management
frames and the optional front doors
16 Front service clearance required for installing
the chassis and replacing the modules
Figure
A-20):
Technical Specifications
OL-23069-07