Appendix A
Technical Specifications
Figure A-18
4
1
Cisco Nexus 7009 chassis
2
Cable management frames
3
Vertical rack-mount post
4
Vertical rack-mount post for neighboring rack 12 Rear service clearance required to replace fan
5
Air intake from cold aisle for the power
supplies
OL-23069-07
Clearances Required for a Front-Mounted Cisco Nexus 7009 Chassis in a Two-Post
Rack
10
17.3 in
9
(43.9 cm)
8
7
1
3
2
5
11
12
13
14
3
4
15
6
16
9
Side clearance required for open rack
installations:
10 Chassis width
11 Side clearance required for open rack
installations:
trays and fabric modules
13 Airflow clearance required between the
chassis and inside of cabinet (if used)
Cisco Nexus 7000 Series Hardware Installation and Reference Guide
Chassis Clearances
If next to another open rack, use 6 inches
(15.2 cm).
If next to a wall, use 11 inches (27.9 cm).
If next to another open rack, use 6 inches
(15.2 cm).
If next to a wall, use 11 inches (27.9 cm).