6.2.3 Connect temperature sensor

When connecting the temperature sensor, national requirements must be observed.
Lubricate the temperature sensor before connecting with heat transfer paste to
increase its functionality.
6.2.3.1 Connection to standard temperature sensor pocket
6
5
4
Fig. 10
6.2.3.2 Connection to an older temperature sensor pocket
7
8
6
5
Fig. 11
1
1. Insert the temperature sensor Pt 500 4 in the
temperature sensor pocket 5 (see
2
Appendix).
2. Fasten the temperature sensor through the
capstan screw 2 and the planned screw
connection 6 .
3. Have the temperature sensor sealed using a
3
lead-sealing socket 1 and the wire seal 3 in
accordance with Fig. 9 by a calibration officer.
1
1. Insert the temperature sensor Pt 500 5 in the
temperature sensor pocket 6 (see Appendix).
2
2. Use the adapter for lead-sealing the connection
2 (see Appendix).
3. Fasten the temperature sensor through the
3
capstan screw 3 and the planned screw
connection 8.
4. Have the temperature senor sealed using a
4
lead-sealing socket 1 and the wire seal 4, 7 by
a calibration officer.