Honeywell EK205-M Operating Instructions Manual page 106

Volume conversion device
Table of Contents

Advertisement

106
Message
Description, process
T Alarm Lim.
The gas temperature measured is outside the permissible limits.
The limits can be changed when commissioning in the presence of the
calibration officer. (see section "6.3.1.8", page 44)
p Alarm Lim.
The gas pressure measured is outside the permissible limits.
The limits can be changed when commissioning in the presence of the
calibration officer. (see section "6.3.1.8", page 44)
K-val. error
The compressibility ratio factor could not be calculated, as no valid real gas
factor could be determined yet.
z-fact. err.
The real gas factor could not be calculated. At least one of the gas analysis
values of Ho.n, CO2, H2, Rhon is outside the permissible range.
Vm-Alarm
No volume could be entered for the input used for the volume conversion.
Vm-Inp.Alarm
For the encoder connected on input 1, for 40 seconds (with external, current
supply) or for the duration of two measurement cycles + 1 second (in the
event of battery supply), no operating volume could be entered.
T Inp. error
The gas temperature cannot be measured due to a fault. Please contact the
Elster customer service (see section 1.4 Customer service).
p Inp. error
The gas pressure cannot be measured due to a fault. Please contact the
Elster customer service (see section 1.4 Customer service).
b) Warnings:
Data restore.
The batteries of the EK205-M have failed temporarily. As a result of this, the
time has not changed and no measurements have been logged. However, all
data remain preserved.
This message appears when old batteries are removed before connecting
the new ones (see section 10.2).
Procedure using the enSuite software:
Outp.1 Error
There should be more pulses being emitted from the specified output than
are permitted under its configured settings.
Outp.2 Error
In order to eliminate the cause of the problem, you can use the enSuite
software to either:
In both cases, the change must be aligned with the device connected.
I1-Warning
The encoder could not be read at the end of the measurement period. The
flow recording at this point is invalid.
I2 Pulse cmp
During the pulse comparison between, for instance, input 1 and input 2, too
large a deviation occurred.
W Warn Lim.
The performance displayed is outside the warning limit set.
The warning limit can be changed with the enSuite software.
Set the time of the EK205-M.
Delete the status register
reduce the cp value of the output
or increase the output frequency
Faults