2.
Amplifier
Set the model of the power amplifier corresponding to each audio channel, then set the ports of
RK-ZONE8 which are connected to the output of the power amplifier. The setting must be the
same as the actual connection.
When the amplifier backup function is needed, if the audio signal of the spare power amplifier is
from this device, set the model of the power amplifier in the Spare row, then set the spare ports
of the devices which are connected to the output of the spare power amplifier.
In the Backup Amplifier column, select the spare amplifier corresponding to the main amplifiers
to enable the backup function.
3.
Supervision
Supervision is used to set the related parameters of the supervision function, which is displayed
as below:
Supervision Options
Users can use the software to enable or disable the main power supply, backup power supply
and communication fault. Click the checkbox:
Power Amplifier Loop
The power amplifier loop options are used to enable or disable the supervision of the 100V
cables between controllers and power amplifiers. The options include CH1A, CH1B, CH2A,
CH2B, and spare amplifier.
means enabled.
71