6. Under the dual channel mode, if there are more than 4 zones and the total power rate is more
than 500W, 3 external power amplifiers need to be connected as the following steps:
Use twisted-pair cable to connect PA interface "CH1" of RK-MCU to the PA interface "IN"
-
of the first power amplifier.
Connect the output port "100V" and "COM" of the first power amplifier to RK-MCU input port
-
"CH1B".
Use twisted-pair cable to connect PA interface "CH2" of RK-MCU to the PA interface "IN"
-
of the second power amplifier.
Connect the output port "100V" and "COM" of the second power amplifier to RK-MCU input
-
port "CH2A".
Use twisted-pair cable to connect PA interface "OUT" of the second power amplifier to PA
-
interface "IN" of the third power amplifier.
Connect the output port "100V" and "COM" of the third power amplifier to RK-MCU input
-
port "CH2B".