Rk-Zone8 Zone Expander - Honeywell INTEVIO User Manual

Pa/va system
Table of Contents

Advertisement

RK-ZONE8 Zone Expander

Indicators
Indicator
POWER
MAINS
BACKUP
EARTH
CPU
NETWORK
DCT SHORT
DCT OPEN
POWER
AMPLIFIER
STATUS
SPEAKER
LINE STATUS
Buttons/Switches
Button/Switch Action
Power switch
Color
Status
Description
ON
Power on
Green
Flashing
The device is working in power-saving mode.
OFF
Main power supply works normally.
Yellow
ON
Main power failure is detected.
OFF
Backup power supply works normally.
Yellow
ON
Backup power failure is detected.
OFF
No earth fault is detected.
Yellow
ON
Earth fault is detected in speaker lines.
OFF
CPU works normally.
Yellow
ON
The CPU of MCU is faulty or stops working.
The connection with the MCU is normal or the device is in
OFF
standalone mode.
Yellow
ON
Connection failure to the MCU is detected.
OFF
No short circuit fault is detected on contact inputs.
Yellow
Short circuit fault is detected on the wiring of contact inputs.
ON
For more details, please check the menu of the MCU.
OFF
No open circuit fault is detected on contact inputs.
Yellow
Open circuit fault is detected on the wiring of contact inputs.
ON
For more details, please check the menu of the MCU.
The connection between power amplifier and zone expander
OFF
is normal.
Yellow
Connection failure detected between power amplifier and
ON
zone expander.
OFF
The speaker line is idle.
Normal mode: the group is broadcasting.
Green
ON
Auto. emergency mode: playing alert message in the
speaker line.
Operate live broadcast or playing voice messages in the
Red
ON
speaker line.
Open circuit or short circuit fault is detected in the speaker
Yellow ON
line.
Description
Press
Connect or disconnect main power supply.
95

Advertisement

Table of Contents
loading