■Subnet Address
When communicating with an external device on another Ethernet network through a gateway other than the default gateway,
*1
set the network address
or subnet address
Set a value that satisfies the following conditions.
• The class of the IP address is A, B, or C.
• The host address bits are all "0".
*1 Set the network address of the external device when its class (network address) is different from that of the CC-Link IE TSN Plus
module on the own station.
*2 Set the network address of the external device when its class (network address) is the same as that of the CC-Link IE TSN Plus module
on the own station.
Router 1
Ethernet 1
Setting example 1
External device 1
Class B
IP address: 81044001H (129.4.64.1)
*2
of the external device. (Setting range: 0.0.0.1 to 255.255.255.254)
Own station
Class B
IP address: 81052F01H (129.5.47.1)
Subnet mask: FFFFFC00H (255.255.252.0)
Router 2
Ethernet 2
Setting example 2
External device device 2
Class A
IP address: 71044001H (113.4.64.1)
Ethernet 4
Router 3
Ethernet 3
Setting example 3
External device 3
Class B
IP address: 81052902H (129.5.41.2)
8 PARAMETER SETTINGS
8.1 Parameter Settings for CC-Link IE TSN