Setting the Class3 message communications
To perform Class3 message communications for the EtherNet/IP device, follow the procedure below.
Set Class3 message communications only when the own station operates as a client.
1.
Connect the engineering tool to the originator side and register the EDS file of the target side from the "EtherNet/IP
Configuration" window. ( Page 129 Adding the EDS file)
2.
Select the EtherNet/IP device of the target side in "Module List" and drag it to the list of EtherNet/IP devices.
3.
Set the items such as the device name and IP address of the EtherNet/IP device of the target side.
4.
Double-click "<Detailed Setting>" in the "Connection Setting" column and set the connection of the EtherNet/IP device.
(The setting window that opens from "<Detailed Setting>" of each line is the same.)
5.
Select the EtherNet/IP device under "Scanner" in "Connection List" and click the [Add Connection] button.
6.
Select "Connection (Class3 Message Communications)" in "Select Connection to be Added:" and click the [OK] button.
7.
Set the parameter for the Class3 message communications in "Connection Detailed Setting". ( Page 126
Connections: Scanner (Class3 message communications))
8.
Click the [OK] button to reflect the parameter.
9.
Select [Close with Reflecting the Setting] and close the "EtherNet/IP Configuration" window.
8 PARAMETER SETTINGS