Mitsubishi Electric MELSEC iQ-R Series User Manual page 92

Master/local module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

■Setting example
The following is a setting example to perform interlink transmission from the master station on CC-Link IE TSN to stations on
CC-Link IE Controller Network. In this example, 128-point data input from the slave station (station No.1) is transferred.
No.1
128
1.
Select "0000: RJ71GN11-EIP (T+E) (Master Station) [RX/RWr]" for "Transfer Source Module" and "0020: RJ71GP21-SX
(Normal Station)" for "Transfer Destination Module", and enter the transfer ranges of link devices.
2.
Click the [OK] button.
If the transfer destination network module is on a network other than CC-Link IE TSN, set the transfer
destination link devices within the own station send range of the network module. If the link devices are set
within the send range of another station, the transferred data are overwritten with the send data of another
station.
Master station
(station No.0)
0
8 PARAMETER SETTINGS
90
8.1 Parameter Settings for CC-Link IE TSN
No.0
No.4
RX
LB
RX200
RX27F
LB780
LB7FF
No.3
RX
0 to 3F
1000 to 103F
No.1
No.2
No.3
No.4
No.1
No.2
Network module
LB
0
Set the value to this
area within its own
station send range of
the network module.
1000
Own station send range
Other station send range