When the D LINK LED turns off or is flashing
When the D LINK LED turns off or is flashing, check the following.
Check item
Is the master station operating normally?
Is the master station connected to the network?
Does the IP address of each station match the
"Network Configuration Settings" under "Basic
Settings" of the master station?
In the "Network Configuration Settings" under
"Basic Settings", are the third and fourth octets of
the IP address of the master station overlapped
with those of any other stations?
In the "Network Configuration Settings" under
"Basic Settings", does the network address (subnet
mask part) of the IP address of the master station
match that of other stations?
Are the third and fourth octets of the IP address set
to all 0 or all 1?
Is the host address of the IP address set to all 0 or
all 1?
Is a reserved address set to the IP address?
Do the used Ethernet cables conform to the
Ethernet standard?
Is the switching hub used operating normally?
Does the station-to-station distance meet the
specifications?
Does the cabling condition (bending radius) meet
the specifications?
Is any Ethernet cable disconnected?
Is the connection different from the one set for
"Network Topology" under "Basic Settings" of the
master station?
Has the time synchronization source station been
reset?
Is the time synchronization source station turned
off?
Is the time synchronization source station operating
normally?
Has any other station been reset?
Are other stations turned off?
Are other stations connected to the CC-Link IE TSN
Plus module operating normally?
Is the IP address of another station set?
Is there a station with no IP address set among
other stations?
Are other disconnected stations set in the network
configuration of the master station?
Among other stations, is there a station not set in
the network configuration of the master station?
Is a network topology with restrictions used for
connection?
Are station numbers unique?
Is the IP address overlapped with another station?
Action
• If an error has occurred in the CPU module on the master station, eliminate the cause of the CPU
module error. ( MELSEC iQ-R CPU Module User's Manual (Application))
• If an error occurs in the CC-Link IE TSN Plus module on the master station, take action according to
the module diagnosis procedure. ( Page 368 Module Diagnostics)
Connect the master station to the network.
Correct the setting of the IP address in "Network Configuration Settings" under "Basic Settings" of the
master station.
• Set IP addresses in a way that does not overlap the third to fourth octets of the IP address in all
stations.
• Set the IP address and subnet mask to match the network addresses of all stations.
• Set the third and fourth octets of the IP address to values other than all 0 or all 1.
• Set the host address of the IP address to values other than all 0 or all 1.
• Set an IP address other than a reserved address.
Replace the cables with Ethernet cables which conform to the standard. ( Page 71 Wiring products)
• Use a switching hub that conforms to the standard. ( Page 72 Switching hub (when the system
configured with CC-Link IE TSN))
• Power off and on the switching hub.
Set the station-to-station distance within range. ( Page 60 Performance Specifications of CC-Link IE
TSN)
Refer to the manual for the Ethernet cable, and correct the bending radius.
Replace the Ethernet cable.
Correct the wiring according to "Network Topology" under "Basic Settings" of the master station. (
Page 79 Network Topology)
• Since a station is temporarily disconnected after switching the time synchronization source, wait for it
to return.
• Avoid unnecessary disconnections or returns in a station that is the time synchronization source.
Check the manual of the module used for the time synchronization source station.
• Avoid unnecessary reset, since a station is disconnected while resetting.
• Start other stations.
Power on other stations.
• Check if the modules on the other stations are performing data link using CC-Link IE TSN/CC-Link IE
Field diagnostics. ( Page 372 CC-Link IE TSN/CC-Link IE Field Diagnostics)
• Check the operation status of modules on other stations. ( User's manual for the module used)
Set an IP address to a slave station with no IP address set.
Set the connected slave stations in the network configuration of the master station.
Correct the wiring. ( Page 70 WIRING)
Change the overlapped station number.
Change the IP address of the overlapped station.
15 CHECKING WITH LED