Chapter 5 Part Names - Mitsubishi Electric MELSEC iQ-R Series User Manual

Master/local module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

5
PART NAMES
This chapter describes the part names of the CC-Link IE TSN Plus module.
(1)
(2)
(3)
(4)
(5)
No.
Name
(1)
RUN LED
ERR LED
MST LED
P1
D LINK LED
CC-LINK IE TSN LED
STATUS LED
P2
D LINK LED
CC-LINK IE TSN LED
STATUS LED
(2)
Dot matrix LED
5 PART NAMES
66
Description
Indicates the operating status.
• On: Normal operation
• Off: Error ( Page 364 When the RUN LED turns off)
Indicates the error status of the module. (The LED is always off in offline mode.) ( Page 364
When the ERR LED turns on or is flashing)
• On: Error or error detection on all stations (CC-Link IE TSN)
• Flashing (500ms interval): Data link faulty station detection (CC-Link IE TSN)
• Flashing (200ms interval): Error
• Off: Normal operation
Indicates the operating status of CC-Link IE TSN.
• On: Operating as a master station
• Off: Operating as a local station
Indicates the cyclic transmission status of CC-Link IE TSN. (The LED is always off in offline mode.)
• On: Cyclic transmission being performed
• Flashing: Cyclic transmission stopped
• Off: Disconnected
Indicates the operating status of the network to be used.
• On: Operating in CC-Link IE TSN
• Off: Not used
Always off
Always off
Always off
*3
Indicates the operating status of EtherNet/IP.
• On (green): Data communications being performed
• On (red): Moderate error or serious error ( Page 367 When the STATUS LED turns on in red
or is flashing in red)
• Flashing (green): Failed to establish connection ( Page 367 When the STATUS LED is
flashing in green)
• Flashing (red): Minor error ( Page 367 When the STATUS LED turns on in red or is flashing in
red)
• Off: No error
Indicates the station number of CC-Link IE TSN set for the module.
• Station number or parameter not set: "  "
• Master station: 0
• Local station: 1 to 120
■In module communication test mode
Displays the module communication test result. ( Page 371 Module Communication Test)
■In offline mode
Displays "".
*1
*2