I/O maintenance settings

When using cyclic transmission, set whether to hold or clear output on the sending side or input on the receiving side by using
the following setting of (A), (B), or (C). ( Page 86 Supplementary Cyclic Settings)
• Setting on sending side (A): "Output Mode upon CPU Error" for if a stop error occurred in the CPU module on the sending
side
• Setting on sending side (B): "Output Hold/Clear Setting during CPU STOP" for if the status of the CPU module on the
sending side changed from RUN to STOP
• Setting on receiving side (C): "Data Link Faulty Station Setting" for if the sending side disconnected
[Application Settings]  [Supplementary Cyclic Settings]  [I/O Maintenance Settings]
Input data hold/clear operation on the receiving side
No.0
(A)
(B)
■If a CPU module stop error occurred on the sending side
• If both settings (A) and (B) on the sending side are "Hold", input data on the receiving side is held.
• If setting (A) or (B) on the sending side is "Clear", input data on the receiving side is cleared. (The sending side sends the
data cleared to 0.)
■If the CPU module on the sending side changed from RUN to STOP
• If setting (B) on the sending side is "Hold", input data on the receiving side is held.
• If setting (B) on the sending side is "Clear", input data on the receiving side is cleared. (The sending side sends the data
cleared to 0.)
■If the sending side disconnected
• If setting (C) on the receiving side is "Hold", input data from before disconnection is held on the receiving side.
• If setting (C) on the receiving side is "Clear", input data on the receiving side is cleared.
Devices where hold/clear settings are enabled
The following table and figure show devices for which the settings on the sending side (A)(B) and the setting on the receiving
side (C) are enabled.
Setting to
Setting items
Setting on
Output mode upon
sending side (A)
CPU error
Setting on
Output hold/clear
sending side (B)
setting during CPU
STOP
Setting on
Data link faulty
receiving side (C)
station setting
9 FUNCTIONS
168
9.2 Cyclic Transmission
No.1
(C)
Hold/clear settings are
enabled
• Master station RY
• Local station RY (only the output
data from the own station)
• Master station RY (if the link
refresh source device is other
than Y)
• Local station RY (only the output
data from the own station, and if
the link refresh source device is
other than Y)
• Master station RX
• Local station RX
• Local station RY (only the input
data from other stations)
Hold regardless of setting
• Master station RWw
• Local station RWw (only the
output data from the own station)
• LB (only the output data from the
own station)
• LW (only the output data from the
own station)
• Master station RWr
• Local station RWr
• Local station RWw (only the input
data from other stations)
• LB (only the input data from other
stations)
• LW (only the input data from other
stations)
Clear regardless of setting
• Master station RY (if the link
refresh source device is Y)
• Local station RY (only the output
data from the own station, and if
the link refresh source device is Y)