■Exclusive Owner (originator)
Data sending from the CC-Link IE TSN Plus module (originator) to the target and data receiving from the target to the CC-Link
IE TSN Plus module (originator) can be set simultaneously.
In the above case, the external device must support Exclusive Owner.
The CC-Link IE TSN Plus module supports both point-to-point and multicast for data receiving, and only point-to-point for data
sending.
Scanner
RJ71GN11-EIP
'Class1 Input Area'
(Un\G7348224 to
Un\G7533055)
'Class1 Output Area'
(Un\G7536640 to
Un\G7721471)
(1) Connection open
(2) Response (normal)
■Input Only (originator)
In this application type, only data receiving in the direction from the target to the CC-Link IE TSN Plus module (originator) is
possible.
Both point-to-point and multicast are supported.
RJ71GN11-EIP
'Class1 Input Area'
(Un\G7348224 to
Un\G7533055)
(1) Connection open
(2) Response (normal)
12 FUNCTIONS
262
12.2 Cyclic Transmission Function
Originator
Buffer memory
Buffer memory
Scanner
Originator
Buffer memory
(1)
(2)
Adapter
EtherNet/IP device
(1)
Target
(2)
Send data
(1)
(2)
Adapter
EtherNet/IP device
Target
Send data
Receive data
Adapter
EtherNet/IP device
Target
Send data