Mitsubishi Electric MELSEC iQ-R Series User Manual page 565

Master/local module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Connection with modules on CC-Link IE TSN with a communication speed of 100Mbps
This section describes the network topology when "Communication Speed" under "Application Settings" is set to "100Mbps".
■Line topology
The network is configured in a line topology.
• Adjust the communication speed of the module.
• When connecting modules with different communication speeds, connect the modules via a general-purpose hub.
No.0
No.1
Class B (100Mbps)
Class B (100Mbps)
No.0: Master station (CC-Link IE TSN Plus module)
No.1: Local station
No.2, No.3: Remote station
Class A: CC-Link IE TSN Class A device
Class B: CC-Link IE TSN Class B device
■Star topology
The network is configured in a star topology via a switching hub.
• When the master station with a communication speed of 1Gbps and a remote station with a communication speed of
100Mbps exist in the structure, set "Communication Period Setting" to "Low-Speed" (16 times) for the remote station with a
communication speed of 100Mbps.
No.0
Class B (1Gbps)
No.0: Master station (CC-Link IE TSN Plus module)
No.1, No.2: Remote station
Class A: CC-Link IE TSN Class A device
Class B: CC-Link IE TSN Class B device
• Connect the master station and local station at the same communication speed.
No.0
Class B (100Mbps)
No.1
Class A (100Mbps)
No.0: Master station (CC-Link IE TSN Plus module)
No.1, No.2, and No.3: Local station
Class A: CC-Link IE TSN Class A device
Class B: CC-Link IE TSN Class B device
Appendix 11 Structure of CC-Link IE TSN Class B/A Devices (Protocol Version 1.0 Only) and Ethernet Devices
No.2
No.3
Class B (100Mbps)
Class A (100Mbps)
No.1
Class A (100Mbps)
Low speed
No.2
Class A (100Mbps)
Low speed
No.2
No.0
Class A (100Mbps)
Class B (1Gbps)
No.3
No.1
Class A (100Mbps)
Class A (100Mbps)
No.2
Class A (100Mbps)
No.3
Class A (100Mbps)
APPX