Mitsubishi Electric MELSEC iQ-R Series User Manual page 441

Master/local module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Stored
Stored
Stored
value in (1)
value in (3)
value in (4)
or (2)
or (5)
or (6)
45H (scanner)
11H
0264H
55H (adapter)
45H (scanner)
11H
0266H
55H (adapter)
45H (scanner)
11H
0267H
55H (adapter)
45H (scanner)
11H
0257H
55H (adapter)
45H (scanner)
11H
0262H
55H (adapter)
45H (scanner)
11H
0263H
55H (adapter)
45H (scanner)
11H
Socket error
55H (adapter)
code
46H (scanner)
00H
00CFH
46H (scanner)
10H
00D0H
46H (scanner)
20H
00D0H
50H (adapter)
10H
0000H
50H (adapter)
20H
0284H
53H (adapter)
00H
0136H
Classification Error definition and
causes
Socket error
Socket option setting
error
Socket error
Socket option setting
error
Socket error
Socket option setting
error
Socket error
Socket registration error
Socket error
Socket option setting
error
Socket error
Socket option setting
error
Socket error
IO data send error
The error code obtained
from the communication
stack was set.
Maximum
A connection cannot be
number of
created because the
connections
maximum number of
connections has been
reached.
Maximum
A request cannot be
number of
created because the
requests
maximum number of
requests has been
reached.
Maximum
A request cannot be
number of
created because the
requests
maximum number of
requests has been
reached.
Connection
The connection has
disabled
been set to be disabled.
Connection stop
The connection has
stopped.
Instance
Assembly instance size
registration error
error
Action
• Take measures to reduce noise.
• Reset the CPU module, and run it again. If the same error
occurs again even after taking the above measure, the
possible cause is a hardware failure of the module. Please
consult your local Mitsubishi representative.
• Take measures to reduce noise.
• Reset the CPU module, and run it again. If the same error
occurs again even after taking the above measure, the
possible cause is a hardware failure of the module. Please
consult your local Mitsubishi representative.
• Take measures to reduce noise.
• Reset the CPU module, and run it again. If the same error
occurs again even after taking the above measure, the
possible cause is a hardware failure of the module. Please
consult your local Mitsubishi representative.
• Retry the operation after a while.
• Reset the CPU module, and run it again. If the same error
occurs again even after taking the above measure, the
possible cause is a hardware failure of the module. Please
consult your local Mitsubishi representative.
• Take measures to reduce noise.
• Reset the CPU module, and run it again. If the same error
occurs again even after taking the above measure, the
possible cause is a hardware failure of the module. Please
consult your local Mitsubishi representative.
• Take measures to reduce noise.
• Reset the CPU module, and run it again. If the same error
occurs again even after taking the above measure, the
possible cause is a hardware failure of the module. Please
consult your local Mitsubishi representative.
• Retry the operation after a while.
• Reset the CPU module, and run it again. If the same error
occurs again even after taking the above measure, the
possible cause is a hardware failure of the module. Please
consult your local Mitsubishi representative.
• Check for errors in the line status.
• The line may be busy, so retry the operation after a while.
• Check the parameter set in "EtherNet/IP Configuration"
and write the parameter to the module again.
• Check for errors in the line status.
• The line may be busy, so retry the operation after a while.
• Check the parameter set in "EtherNet/IP Configuration"
and write the parameter to the module again.
• Check for errors in the line status.
• The line may be busy, so retry the operation after a while.
• Check the parameter set in "EtherNet/IP Configuration"
and write the parameter to the module again.
• Check the parameter set in "EtherNet/IP Configuration"
and write the parameter to the module again.
• If the same error code is displayed again, the possible
cause is a hardware failure of the error module. Please
consult your local Mitsubishi representative.
• Check whether the operating status of the external device
is normal.
• Check for errors in the line status.
• The line may be busy, so retry the operation after a while.
• Check the parameter set in "EtherNet/IP Configuration"
and write the parameter to the module again.
• If the same error code is displayed again, the possible
cause is a hardware failure of the error module. Please
consult your local Mitsubishi representative.
19 LIST OF ERROR CODES
19.3 Error Codes When a Connection Error Occurs
19
439