■Connections: Scanner (Input Only (Class1 Instance))
The following image shows an example of the window when a CC-Link IE TSN Plus module connection is added.
Item
Connection Name
Application Type
Connection No.
Communication Method
Comment
Trigger Type
Inhibit Time Mode
Inhibit Time
Timeout Multiplier
8 PARAMETER SETTINGS
122
8.2 EtherNet/IP Parameter Settings
Description
Displays the connection name.
Displays the application type.
Set the connection number.
The default value is the minimum value from the unused connection
numbers in the connection list.
Displays the communication method.
Set comments to the connection if required.
Set the trigger type to be used in combination with "RPI" to control the
timing of data sending.
The setting items depend on the EtherNet/IP device to be used.
• Cyclic: Data is sent periodically according to "RPI".
• Change of State: Data is sent when the status changes.
This is fixed to "Cyclic" if the adapter is a CC-Link IE TSN Plus module.
Set the mode of the transmission inhibit time (minimum delay time) until
transmission.
This item can be set only when "Trigger Type" is set to "Change of
State".
• Default: 1/4 of "RPI" of Output (O->T) is used as "Inhibit Time".
However, if the value exceeds 255ms, 255ms is used.
• Un-Activated: 0ms is used as "Inhibit Time".
• Custom: Enter a value directly in "Inhibit Time".
This is fixed to "Default" if the adapter is a CC-Link IE TSN Plus module.
Set the transmission inhibit time (minimum delay time) until
transmission. (Unit: ms)
This item can be set only when "Inhibit Time Mode" is set to "Custom".
If "Inhibit Time Mode" is set to "Default", automatic calculation will be
performed.
Set the timeout multiplier.
*1
Setting range
001 to 256
(Default: Refer to the left.)
Up to 32 characters (one-byte
or two-byte)
(Default: empty)
• Cyclic
• Change of State
(Default: Cyclic)
• Default
• Un-Activated
• Custom
(Default: Default)
1 to 255
(Default: 1/4 the value of "RPI"
of Output (O->T) is used.)
• 4
• 8
• 16
• 32
• 64
• 128
• 256
• 512
(Default: 4)

Advertisement