Mitsubishi Electric MELSEC iQ-R Series User Manual page 566

Master/local module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

• When "Communication Mode" is set to "Multicast" and the communication speed of the master station is 1Gbps,
communication may not be possible depending on the type of the device if slave stations with different communication
speeds of 1Gbps and 100Mbps coexist on the end side via the switching hub. The communication will be enabled by
configuring settings with the switching hub so that the multicast frame (with multicast MAC address 09:00:70:00:10:02 and
09:00:70:00:10:05) will not be transferred to the port of the slave station with 100Mbps.
No.0
Class B (1Gbps)
No.1
Class A (100Mbps)
No.0: Master station (CC-Link IE TSN Plus module)
No.1, No.2, and No.3: Remote station
Class A: CC-Link IE TSN Class A device
Class B: CC-Link IE TSN Class B device
APPX
564
Appendix 11 Structure of CC-Link IE TSN Class B/A Devices (Protocol Version 1.0 Only) and Ethernet Devices
No.2
Class A (100Mbps)
No.3
Class A (1Gbps)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec iq-r cc-link ie tsn plus

Table of Contents