Setting the Class1 tag communications
To perform Class1 tag communications for the EtherNet/IP device, follow the procedure below.
1.
Connect the engineering tool to the originator side and register the EDS file of the target side from the "EtherNet/IP
Configuration" window. ( Page 129 Adding the EDS file)
2.
Select the EtherNet/IP device of the target side in "Module List" and drag it to the list of EtherNet/IP devices.
3.
Set the items such as the device name and IP address of the EtherNet/IP device of the target side.
4.
Double-click "<Detailed Setting>" in the "Connection Setting" column and set the connection of the EtherNet/IP device.
(The setting window that opens from "<Detailed Setting>" of each line is the same.)
5.
Configure the settings to send data to "Consumer" (target) using the own station (originator) as "Producer".
Select the EtherNet/IP device under "Scanner" in "Connection List" and click the [Add Connection] button.
6.
Select "Input Only (Class1 Tag)" in "Select Connection to be Added:" and click the [OK] button.
7.
Set the parameter for the Class1 tag communications in "Connection Detailed Setting". ( Page 124 Connections:
Scanner (Input Only (Class1 Tag)))
• For "Tag Name", set the tag name of the connection you wish to communicate with as the target.
• For "Data Size" under "Input T->O", set the data size of the connection you wish to communicate with as the
target.
8 PARAMETER SETTINGS
132
8.2 EtherNet/IP Parameter Settings