Station Information List - Mitsubishi Electric MELSEC iQ-R Series User Manual

Master/local module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Precautions
• When a relay sending station is set to "Target Station", the communication test ends with an error. Set a relay receiving
station to "Target Station".
Network No.1
Station
Station
No.0
No.1
Own station
Relay receiving
(request source)
station
• When "Network No./Station No." is selected for "Communication Method" and a station mounted on the same base unit
(main base unit and extension base unit) is set to "Target Station", the communication test ends with an error.
• Whether or not transient transmission can be executed from the connected station (own station) to a station in another
network by specifying an IP address cannot be checked.
• Since this function uses PING, a communication test target station communication error (error code D919H) occurs if the
communication target does not respond to PING. When executing this function, check if the security setting (such as
firewall) of the communication target is set to respond to PING. Moreover, if the target is set not to respond to PING in the
security settings (such as a firewall), it may take some time until a timeout error occurs on the engineering tool. For details
on when communication using the engineering tool is not allowed in the settings of Windows Firewall, refer to the following.
 GX Works3 Operating Manual

Station Information List

The station information list displays information of the slave stations which are performing data link in list form.
Item
Number of Stations
Change IP Address Display
Station No.
Model Name
IP Address
MAC Address
F/W Version
Production Information
Module Inherent Information
*1 Displays the information of P1 when the CC-Link IE TSN Plus module is connected as a slave station.
• The station information list displays only the slave stations which are performing data link.
• If the engineering tool does not have information of the relevant slave station, "" is displayed for each
item.
• If the relevant slave station is an unsupported module, "Other Modules" is displayed.
Network No.2
Station
Station
No.2
No.0
Relay sending
station
Description
Displays the number of slave stations to be displayed in the station information list.
Select an IP address display format.
Displays the station number of the slave station.
Displays the model name of the slave station.
Displays the IP address of the slave station.
Displays the MAC address of the slave station.
Displays the firmware version of the slave station.
Displays the production information of the slave station.
Displays the module-specific information of the slave station.
*1
*1
17 CHECKING THE NETWORK STATUS
17.1 Checking the Status of CC-Link IE TSN
17
383

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec iq-r cc-link ie tsn plus

Table of Contents