Mitsubishi Electric MELSEC iQ-R Series User Manual page 102

Master/local module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Simple
Detailed
display
display
CC-Link IE TSN Class
*1 When the settings cannot be determined with the module parameter and "Network Configuration Settings," a hyphen or incorrect
calculation result may be displayed.
*2 If a setting is present for "Subnet Mask" under "Station No./IP Address Setting Method" in "Required Settings", this value shall be set as
the default.
*3 If "CC-Link IE TSN Class Setting" of a general CC Link IE TSN module added to list of stations in "Network Configuration Settings" is set
to CC-Link IE TSN Class A and the communication period interval and minimum value for cyclic transmission time are set to
"Communication Period Interval Setting" and "Cyclic Transmission Time", the cyclic transmission may not be possible. In this case,
select the actual device to be used from "Module List" and add it to list of stations, or refer to the manual for the device to be used to
check the maximum response time for the time managed polling method and calculate and set the communication period interval and
cyclic transmission time.
*4 If the number of assigned link device points exceeds the number of assignable points at a station whose CC-Link IE TSN Class is CC-
Link IE TSN Class A, a link device point number error (error code: 3160H) will occur. For details on the number of points to which CC-
Link IE TSN Class A slave stations can be assigned, refer to the following.
Page 100 Number of link device points to which CC-Link IE TSN Class A slave stations can be assigned
Because a portion of the setting items are not displayed in simple display, when there are deficiencies in
setting items that are not displayed, the "Output" window may display a warning or error by selecting [Close
with Reflecting the Setting].
If a warning is displayed, switch to detailed display and correct the items.
■Number of link device points to which CC-Link IE TSN Class A slave stations can be assigned
The number of link device points to which CC-Link IE TSN Class A slave stations can be assigned must satisfy the following
two conditional formulae.
• (Number of points of "RY setting"  8) + (Number of points of "RWw setting"  2)  1916
• (Number of points of "RX setting"  8) + (Number of points of "RWr setting"  2)  1876
8 PARAMETER SETTINGS
100
8.1 Parameter Settings for CC-Link IE TSN
Description
Set the CC-Link IE TSN Class of the device for each slave station.
Setting range
*4
• CC-Link IE TSN Class B
• CC-Link IE TSN Class A
(Default: Varies depending on the
device)