Error
Error definition and causes
code
C054H
The number of read/write points from/to
the random device of SLMP message is
out of the allowable range in the CPU
module (in units of words, double words).
C055H
The read/write size from/to the file data of
SLMP message is out of the allowable
range.
C056H
The read/write request exceeds the largest
address.
C057H
The request data length of the SLMP
message does not match the number of
data in the character (a part of text).
C058H
The request data length of the SLMP
message after the ASCII/binary conversion
does not match with the number of data in
the character (a part of text).
C059H
• The specified command and
subcommand of the SLMP message are
incorrect
• A function that is not supported by the
target device was executed.
C05AH
The CC-Link IE TSN-equipped module
cannot read/write data from/to the device
specified in the SLMP message.
C05BH
The CC-Link IE TSN-equipped module
cannot read/write data from/to the device
specified in the SLMP message.
C05CH
The received request data of the SLMP
message is incorrect.
C05DH
The "Monitor Request" command is
received before the monitor registration is
performed by the "Monitor Registration/
Clear" command of the SLMP message.
C05EH
• The time between reception of the
SLMP message by the CC-Link IE TSN-
equipped module and the returned
response from the access destination
exceeded the monitoring timer value set
in the SLMP command.
• An unresponsive command was sent to
another network station as the access
destination. (If this error does not cause
any problems, it can be ignored.)
C05FH
This request cannot be executed to the
access destination specified by the SLMP
message.
C060H
The request details for bit devices of the
SLMP message is incorrect.
C061H
• The request data length of the SLMP
message does not match the number of
data in the character (a part of text).
• The write data length specified by the
label write command is not even byte.
C06FH
The network number of request destination
specified by the SLMP request message is
not available for communications with the
station number 121 or larger.
Action
Correct the number of read/write points and send the SLMP message to the
CC-Link IE TSN-equipped module again.
Correct the number of read/write points and send the SLMP message to the
CC-Link IE TSN-equipped module again.
• Correct the start address or the number of read/write points so that the
request does not exceed the largest address, and send the data to the
CC-Link IE TSN-equipped module again.
• If the access target and connection stations are modules of the MELSEC
iQ-R series, send the SLMP message to the CC-Link IE TSN-equipped
module again using subcommands 003 and 002.
Check and correct the text or request data length, and send the SLMP
message to the CC-Link IE TSN-equipped module again.
Check and correct the text or request data length, and send the SLMP
message to the CC-Link IE TSN-equipped module again.
• Check that there are no errors in the specification of the command and
subcommand of the SLMP message.
• Check whether the function executed is supported by the target device.
• Check the version of the target device.
Correct the specification of the device to be read/written and send the SLMP
message to the CC-Link IE TSN-equipped module again.
Correct the specification of the device to be read/written and send the SLMP
message to the CC-Link IE TSN-equipped module again.
Correct the request data and send the SLMP message to the CC-Link IE
TSN-equipped module again.
Register the monitoring data using "Monitor Registration/Clear" command
and perform monitoring.
• Increase the monitoring timer value.
• Check if the access destination is operating normally.
• Correct the network number or request destination station number.
• If the access destination is a module with a different network number,
correct the routing parameter setting.
• If the access destination is a module with a different network number,
check if the network number is not in use.
Correct the access destination.
Correct the request details and send the SLMP message to the CC-Link IE
TSN-equipped module again.
• Check and correct the text or request data length, and send the SLMP
message to the CC-Link IE TSN-equipped module again.
• Add one byte of dummy data, and specify the length as an even number
of bytes.
• If the 3E or 4E frame is used at SLMP, check that there is no error for the
network number of the request destination and station number.
• If the station number extension frame is used at SLMP, check that there is
no error for the network number of the request destination and station
number.
19 LIST OF ERROR CODES
19.1 Error Codes When a Module Error Occurs
Detailed
information 1
Detailed
information 2
19
417