■Connections: Scanner (Class3 message communications)
Item
Connection Name
Connection No.
Communication Method
Service
Data Size
Comment
Trigger Type
RPI
Timeout Multiplier
Class ID
Instance ID
Attribute ID
8 PARAMETER SETTINGS
126
8.2 EtherNet/IP Parameter Settings
Description
Displays the connection name.
Set the connection number.
The default value is the minimum value from the unused connection numbers
in the connection list.
Displays the communication method.
Set the service ID.
Set the data size. (Unit: Bytes)
Set comments to the connection if required.
Set the trigger type to be used in combination with "RPI" to control the timing
of data sending.
• Cyclic: Class3 messages are sent periodically according to "RPI".
• Application Trigger: Class3 messages are sent according to the request
from the client (own station).
Set the request packet interval (RPI). (Unit: 500s)
Set the timeout multiplier.
Set the class ID.
Set the instance ID.
Set the attribute ID.
Setting range
001 to 256
(Default: Refer to the left.)
0 to 255
(Default: 0)
0 to 1404
(Default: 0)
Up to 32 characters (one-byte or two-
byte)
(Default: empty)
• Cyclic
• Application Trigger
(Default: Cyclic)
200000 to 60000000
(Default: 200000)
• 4
• 8
• 16
• 32
• 64
• 128
• 256
• 512
(Default: 4)
0 to 65535
(Default: 0)
0 to 65535
(Default: 0)
0 to 65535
(Default: 0)