Mitsubishi Electric MELSEC iQ-R Series User Manual page 488

Master/local module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Intelligent auto refresh status
■Intelligent auto refresh status (Un\G7340033)
The state of the setting for whether or not auto refresh applied to Class1 communications input or output data is stored as the
initial value.
*1
If auto refresh
for input data and auto refresh
than 0.
*1 Data transferred from network module to CPU module
*2 Data transferred from CPU module to network module
• 0: Auto refresh is not set.
• 1: Auto refresh is set only for output data.
• 2: Auto refresh is set only for input data.
• 3: Auto refresh is set for input and output data.
For auto refresh settings, refer to the following.
Page 114 Refresh Setting
PING test request area
■PING test request area (Un\G7340048 to Un\G7340051)
This area executes a PING test request.
Address
Un\G7340048
Un\G7340049
Un\G7340050 to Un\G7340051
*1 This refers to the bits where the subnet mask is 0. If the subnet mask is not set, the following subnet masks are applied depending on
the own station IP address class.
Class A (IP address leading bit string is 0)  Subnet mask: 255.0.0.0
Class B (IP address leading bit string is 10)  Subnet mask: 255.255.0.0
Class C (IP address leading bit string is 110)  Subnet mask: 255.255.255.0
APPX
486
Appendix 3 Buffer Memory
*2
for output data are set for even a single connection, the value will be other
Item
Communication time check
Transmission count
IP Address
Description
Specifies the PING test end waiting time.
• 0: Operations are performed after one second.
• 1 to 5: Operations are performed after the set value. (Unit: seconds)
• 6 or higher: Operations are performed after five seconds.
Specifies the transmission count.
• 0: One transmission is performed.
• 1 to 10: Transmissions are performed for the specified number of
transmissions. (Unit: times)
• 11 or higher: 10 transmissions are performed.
Specifies the IP address of the PING test target device.
• Un\G7340050: Lower-order word of IP address
• Un\G7340051: Higher-order word of IP address
■Allowable IP address setting range
• 1.0.0.1 to 126.255.255.255
• 128.0.0.0 to 223.255.255.254
Please note that the following IP addresses cannot be set.
• Own station IP address
• The network address of the network to which the own station belongs. (IP
address where all bits indicating the host
• The broadcast address of the network to which the own station belongs. (IP
address where all bits indicating the host
■Example
If the IP address of the own station is 192.168.3.4 and the subnet mask is
255.255.0.0, the following addresses cannot be set.
• Own station IP address: 192.168.3.4
• Network address: 192.168.0.0
• Broadcast address: 192.168.255.255
*1
are 0.)
*1
are 1.)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec iq-r cc-link ie tsn plus

Table of Contents