Chapter 8 Parameter Settings; Parameter Settings For Cc-Link Ie Tsn; Procedure For Setting Parameters - Mitsubishi Electric MELSEC iQ-R Series User Manual

Master/local module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

8
PARAMETER SETTINGS
8.1

Parameter Settings for CC-Link IE TSN

This chapter describes the parameter settings required for communications with other stations of CC-Link IE TSN.

Procedure for setting parameters

1.
Add the CC-Link IE TSN Plus module (RJ71GN11-EIP) to the engineering tool.
[Navigation window]  [Parameter]  [Module Information]  Right-click  [Add New Module]
2.
The required settings, basic settings, and application settings are included in the parameter settings. Select one of the
settings from the tree on the window shown below.
[Navigation window]  [Parameter]  [Module Information]  Target module  [Port1 Module Parameter (CC-Link IE
TSN)]
3.
After setting the parameters, click the [Apply] button.
4.
Write parameters to the CPU module using the engineering tool.
[Online]  [Write to PLC]
5.
The parameters are reflected by resetting the CPU module or powering off and on the system.
The settings displayed on the required settings, basic settings, and application settings pages (default: ) are
the values that are displayed when the [Restore the Default Settings] button on each window of the
engineering tool is clicked.
8 PARAMETER SETTINGS
8.1 Parameter Settings for CC-Link IE TSN
8
73