Setting Teamwork Control Parameters - Huawei NetCol8000-C070 User Manual

In-room chilled water smart cooling product
Hide thumbs Also See for NetCol8000-C070:
Table of Contents

Advertisement

NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Parameter
Max indoor fan speed
----End

4.5.3 Setting Teamwork Control Parameters

Prerequisites
The teamwork group number and addresses for the smart cooling products have
been set as follows:
Context
The parameters in this section are for reference only. Set actually parameter values
as required.
Procedure
Step 1 On the home screen, tap
Settings screen, as shown in
Figure 4-4 Teamwork Settings
Step 2 Set teamwork control parameters.
All teamwork control parameters can be set on the master smart cooling product.
Only Teamwork group No., Air conditioner address, Enable teamwork CAN
resistor, Teamwork function and Networking mode can be set on slave smart
cooling products. Other parameters of the slave units will be modified by the
master unit synchronously.
Issue 07 (2021-12-30)
Teamwork group No.: Group the smart cooling products in adjacent areas as
one, that is, assign one teamwork group number for them. At most four
teamwork control groups can be set (1–4).
System address: The address (configurable range: 1–32) of each smart cooling
product in the same group must be unique. The smart cooling product with
the smallest unit address is the master unit, which collects, processes, and
delivers group data. The recommended value range is 1 to the number of
units in the group.
Copyright © Huawei Technologies Co., Ltd.
Description
Sets the maximum speed
for the indoor fan.
> Teamwork Settings, to enter the Teamwork
Figure
4-4.
Table 4-6
describes how to set the parameters.
4 Power-On Commissioning
Configuration Principle
The default value is
100%. You are advised
not to change the value.
103

Advertisement

Table of Contents
loading

Table of Contents