Menu
Settings >
System
Settings >
T/H sensor
Settings >
System
Settings >
Indoor fan
Issue 07 (2021-12-30)
Name
Temperature and
humidity control
type
Temperature
control mode
Temperature
setpoint
Humidity setpoint
Return air sensor
Cold aisle sensor
Hot aisle sensor
Indoor fan control
type
Copyright © Huawei Technologies Co., Ltd.
Parameter Description
Cold aisle, Hot aisle,
Return air, or Supply air
can be set as required. The
temperature and humidity
set points correspond to
the selected control type
can be set.
Set the temperature inside
the room or aisles based
on the Average value,
Max value, or Min value
of the temperatures
collected by each sensor.
After the temperature and
humidity control type and
the temperature value
under this type are set, the
device performs cooling or
heating based on the
settings.
After the temperature and
humidity control type and
the humidity value under
this type are set, the device
performs humidifying or
dehumidifying based on
the settings.
The return air sensors can
be set to Enable or
Disable.
The sensors in cold aisles
can be set to Enable or
Disable.
The sensors in hot aisles
can be set to Enable or
Disable.
R/S air temp diff rate ctrl,
R/S air temp diff ctrl, or
Pressure diff ctrl can be
set.
E Parameter Description
Default Value
Supply air
Average value
22.0°C
50.0%RH
Disable
Disable
Disable
R/S air temp
diff rate ctrl
240