Optional) Installing Teamwork And Monitoring Communications Cables; Preparing A Network Cable - Huawei NetCol8000-C070 User Manual

In-room chilled water smart cooling product
Hide thumbs Also See for NetCol8000-C070:
Table of Contents

Advertisement

NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
3.6.4 (Optional) Installing Teamwork and Monitoring
Communications Cables
● Units of different models and software versions cannot be networked for
teamwork.
● Connect teamwork and monitoring communications cables based on the
networking scenario.
● The teamwork communications cable must be a shielded network cable of Cat
5e or higher specifications. The network cable length between adjacent units
must be less than or equal to 100 m, and the maximum distance for CAN
teamwork communication must be less than or equal to 310 m.
● Route cables in compliance with local standards. Take appropriate shielding
measures, such as using a galvanized pipe or an ELV cable tray, to reduce the
impact of electromagnetic interference on teamwork communication.
Otherwise, teamwork networking may fail.

3.6.4.1 Preparing a Network Cable

Step 1 Crimp a network cable.
Figure 3-42 Teamwork communications cable and FE monitoring communications
cable
(1) White-and-orange (2) Orange
(5) White-and-blue
Issue 07 (2021-12-30)
NO TICE
(6) Green
Copyright © Huawei Technologies Co., Ltd.
(3) White-and-green
(4) Blue
(7) White-and-brown
(8) Brown
3 Installation