4.4.4 Setting Teamwork Control Parameters

Prerequisites
Assign teamwork group number and teamwork unit address for the teamwork
controlled smart cooling products as follows:
Context
The parameters in this section are for reference only. Set actually parameter values
as required.
Procedure
Step 1 On the home screen, tap
Settings page, as shown in
Figure 4-19 Teamwork settings
Step 2 Set teamwork control parameters.
All teamwork control parameters can be set on the master smart cooling product.
Only Teamwork group No., Smart cooling product address, Enable teamwork
CAN resistor, Teamwork function and Networking mode can be set on slave
smart cooling products. Other parameters of the slave units will be modified by
the master unit synchronously.
Issue 06 (2020-08-19)
Teamwork group no.: Group the smart cooling products in adjacent areas as
one, that is, assign one teamwork group number for them. At most four
teamwork groups can be assigned (1–4).
Teamwork unit address: The address for the smart cooling product in the
same group cannot be the same (address range: 1–32). The smart cooling
product with minimum address is the master one that collects, processes, and
delivers data.
Copyright © Huawei Technologies Co., Ltd.
> Teamwork Settings, to enter Teamwork
Figure
4-19.
Table 4-8
describes how to set the parameters.
4 Power-on and Commissioning
97