NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Menu
Issue 07 (2021-12-30)
Name
Supply air low
temperature
alarm
Return air high
temperature
alarm
Return air low
temperature
alarm
Cold aisle high
temperature
alarm
Cold aisle low
temperature
alarm
Hot aisle high
temperature
alarm
Hot aisle low
temperature
alarm
High humidity
alarm
Low humidity
alarm
Copyright © Huawei Technologies Co., Ltd.
Parameter Description
An alarm is generated
when the detected value is
less than the corresponding
threshold.
An alarm is generated
when the system detects
that the value exceeds the
corresponding threshold.
An alarm is generated
when the system detects
that the value exceeds the
corresponding threshold.
An alarm is generated
when the system detects
that the value exceeds the
corresponding threshold.
An alarm is generated
when the system detects
that the value exceeds the
corresponding threshold.
An alarm is generated
when the system detects
that the value exceeds the
corresponding threshold.
An alarm is generated
when the system detects
that the value exceeds the
corresponding threshold.
An alarm is generated
when the system detects
that the value exceeds the
corresponding threshold.
An alarm is generated
when the system detects
that the value exceeds the
corresponding threshold.
E Parameter Description
Default Value
5.0°C
45.0°C
15.0°C
40.0°C
10.0°C
45.0°C
15.0°C
85.0%RH
20.0%RH
228