Parameter
DO_1
DO_2
Copyright © Huawei Technologies Co., Ltd.
4 Power-On Commissioning
Description
● If this parameter is set to Smoke &
Water only, DO_1 acts according to
DO_1 action when a smoke or water
overflow alarm is generated.
● If this parameter is set to Critical alarm,
DO_1 acts according to DO_1 action
when a critical alarm is generated.
● If this parameter is set to Major alarm,
DO_1 acts according to DO_1 action
when a major alarm is generated.
● If this parameter is set to Alarm, DO_1
acts according to DO_1 action when a
critical alarm, major alarm, or warning is
generated.
● If this parameter is set to Startup status,
DO_1 acts according to DO_1 action
when the unit is started.
● If this parameter is set to No, no alarm is
generated when DO_1 is disconnected.
● If this parameter is set to Smoke &
Water only, DO_2 acts according to
DO_2 action when a smoke or water
overflow alarm is generated.
● If this parameter is set to Critical alarm,
DO_2 acts according to DO_2 action
when a critical alarm is generated.
● If this parameter is set to Major alarm,
DO_2 acts according to DO_2 action
when a major alarm is generated.
● If this parameter is set to Alarm, DO_2
acts according to DO_2 action when a
critical alarm, major alarm, or warning is
generated.
● If this parameter is set to Startup status,
DO_2 acts according to DO_2 action
when the unit is started.
● If this parameter is set to No, no alarm is
generated when DO_2 is disconnected.
● If this parameter is set to Power
abnormal, DO_2 acts according to DO_2
action when a power exception alarm is
generated.
95