Huawei NetCol8000-C070 User Manual page 117

In-room chilled water smart cooling product
Hide thumbs Also See for NetCol8000-C070:
Table of Contents

Advertisement

NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Parameter
Hot aisle temperature
and humidity sharing
Step 3 Complete the teamwork settings for all the smart cooling products by performing
Step 1
Step 4 On the home screen of the display module of any teamwork controlled smart
cooling product, tap
topology of the smart cooling product in the group is displayed.
Figure 4-5 Teamwork topology
No.
1
2
Issue 07 (2021-12-30)
Description
This function can be enabled only when at least one
smart cooling product in the group is equipped with
hot aisle T/H sensors. If this function is enabled, the
master unit in the teamwork group collects the hot
aisle temperature and humidity values from all units
equipped with hot aisle sensors, and synchronizes
the temperature and humidity values to all units
after logical calculation.
After this function is enabled, the master unit
synchronizes the temperature and humidity control
type and setpoints to all slave units.
and
Step
2.
. If the teamwork control succeeds, the teamwork
Item
On/Off
01/02/03...
Copyright © Huawei Technologies Co., Ltd.
Note
● On: The device is started.
● Off: The device is shut down.
Indicates the device address. The smallest
address is for the master unit and the rest are
for slave units.
If the master unit is offline, the online device
with the smallest address is selected to be the
new master.
4 Power-On Commissioning
107

Advertisement

Table of Contents
loading

Table of Contents