Huawei NetCol8000-C070 User Manual page 252

In-room chilled water smart cooling product
Hide thumbs Also See for NetCol8000-C070:
Table of Contents

Advertisement

NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Menu
Settings >
System
Settings >
Humidifier
Settings >
System
Settings >
Cooling
cap. mgmt
Maint >
Performanc
e Maint
Maint >
Sensor
Calibration
Issue 07 (2021-12-30)
Name
-
Cooling capacity
management
function
Chilled water
valve total
runtime
Indoor fan total
runtime
Elec heater total
runtime
Total open times
of the water inlet
solenoid value
Humidifier total
runtime
Return air filter
total runtime
Fresh air filter
total runtime
Supply air
temperature
calibration value
Return air
temperature
calibration value
Return air
humidity
calibration value
Supply water
temperature
calibration value
Return water
temperature
calibration value
Copyright © Huawei Technologies Co., Ltd.
Parameter Description
-
The cooling capacity
management function can
be set to Enable or
Disable.
Total runtime of the chilled
water valve.
Total runtime of the indoor
fan.
Total runtime of the
electric heater.
Total open times of the
water inlet solenoid value.
Total runtime of the
humidifier.
Total runtime of the return
air filter.
Total runtime of the fresh
air filter.
Specifies the adjustment
value of each sensor when
the detected temperature
or humidity varies from the
practical value. For
example, if the detected
return air temperature is
1°C lower than the value
detected by other devices,
set the calibration value to
1°C.
E Parameter Description
Default Value
-
Disable
0h
0h
0h
0
0h
0h
0h
0.0°C
0.0°C
0.0%RH
0.0°C
0.0°C
242