Figure 3-5 Layout of side pipe routing
(1) NetCol8000-C

3.1.4 Installation Requirements

If the water inlet temperature exceeds 10°C or the total load is less than 30% of
the cooling capacity of a single smart cooling product, the humidity may be high.
The customer is advised to add a dehumidifier (engineering procurement).
Pipe Ports
The following table lists the pipe ports reserved on the NetCol8000-C.
Issue 07 (2021-12-30)
NO TE
● This installation method is not recommended for upflow units.
● The height of the raised floor for downflow units must be greater than 550 mm. (The
550 mm space under the floor is used only for fan rotation. The fan rotation area
cannot be occupied by pipes or cables.) Properly determine the positions for routing
pipes and cables to avoid interference.
● L indicates the front maintenance distance, and the minimum L is 900 mm. If this
requirement cannot be met, the minimum L after front doors are removed can be 800
mm.
NO TE
● W indicates the distance between smart cooling products, and the minimum W is 600
mm.
● L indicates the front maintenance distance, and the minimum L is 900 mm. If this
requirement cannot be met, the minimum L after front doors are removed can be 800
mm.