NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Table 4-4 Parameter description
Parameter
Temperatur
e and
humidity
control type
Temperatur
e control
mode
Temperatur
e setpoint
Issue 07 (2021-12-30)
Description
Cold aisle, Hot aisle, Return
air, or Supply air can be set as
required. The temperature and
humidity set points correspond
to the selected control type can
be set.
This parameter controls the
temperature inside the room or
aisles based on the Average
value, Max value, or Min
value of the temperatures
collected by each sensor.
After the temperature and
humidity control type and the
temperature value under this
type are set, the device
performs cooling or heating
based on the settings.
Copyright © Huawei Technologies Co., Ltd.
4 Power-On Commissioning
Configuration Principle
● When the application
scenario is cold or hot aisle
containment, you are
advised to choose Cold aisle
if the cold aisle T/H sensors
are configured, and choose
Supply air if the cold aisle
T/H sensors are not
configured.
● When the application
scenario is non-aisle
containment, you are
advised to choose Return
air, and choose Cold aisle if
the cold aisle T/H sensors
are configured.
● Hot aisle is not
recommended.
● Average value: Select
Average value if the
temperature is to be
controlled based on the
averaged data value
collected by the collector.
● Max value: Select Max
value if the temperature is
to be controlled based on
the maximum data value
collected by the collector.
● Min value: Select Min value
if the temperature is to be
controlled based on the
minimum data value
collected by the collector.
Set this parameter as required.
● Return air: 26–35°C
recommended
● Supply air: 18–24°C
recommended
● Cold aisle: 18–24°C
recommended
● Hot aisle: 26–35°C
recommended