Table 3-8 Description about the cables of the NetCol8000-C130/NetCol8000-C190
Applica
tion
Scenari
o
Indoor
unit
Teamwo
rk and
monitor
ing
network
cables
Issue 07 (2021-12-30)
Name
Technical Requirements
Power cable
Electrical power cable, 600
(without
V/1000 V, ZA-RVV, 5 x 4
heating and
mm
humidification)
red, yellow, green, blue,
black), 32 A, outdoor cable,
CE
Power cable
Electrical power cable, 600
(with heating
V/1000 V, ZA-RVV, 5 x 6
and
mm
humidification)
red, yellow, green, blue,
black), 32 A, outdoor cable,
CE
Equipotential
Greater than or equal to 6
ground cable
mm
Standard
Signal cable, shielded
network cable
straight-through cable, 10 m,
MP8-II, CC4P0.5GY(S), MP8-
II, FTP
Copyright © Huawei Technologies Co., Ltd.
2
, black (five core wires:
2
, black (five core wires:
2
3 Installation
Remarks
The length is
determined based
on the pre-sales
engineering survey.
The neutral wire is
not required for the
power input to the
product. Cut the
blue neutral wire
onsite and wrap
the exposed part
using insulation
tape. You can also
purchase 4-core
power cables in
advance.
The length is
determined based
on the pre-sales
engineering survey.
The neutral wire is
not required for the
power input to the
product. Cut the
blue neutral wire
onsite and wrap
the exposed part
using insulation
tape. You can also
purchase 4-core
power cables in
advance.
The length is
determined based
on engineering
survey.
The length is
determined based
on engineering
survey.