NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Table 4-6 Teamwork settings
Parameter
Teamwork group No.
System address
Enable teamwork CAN
resistor
Teamwork function
Networking mode
Teamwork parameter
synchronization
Number of systems in
this group
Number of running
systems in this group
Issue 07 (2021-12-30)
Description
Specifies the planned teamwork group number. This
parameter should be the same for all units in the
same teamwork group.
Specifies the planned unit address. The addresses of
units in the same teamwork group must be unique.
If CAN network is selected, set Enable teamwork
CAN resistor to Yes for the first and last units. If
Enable teamwork CAN resistor is set to No for the
first and last units, the CAN communication quality
will be affected, and even the teamwork CAN
networking will fail.
Yes: The teamwork control CAN resistor is enabled
for the unit.
No: The teamwork control CAN resistor is disabled
for the unit.
Specifies whether to enable the teamwork function.
Set this parameter based on onsite heat load
distribution.
● Disable: A unit operates independently.
● Enable: A unit operates in team with other units.
Specifies the networking mode for teamwork control.
The networking mode selected on the screen must
match the actual networking mode. Otherwise, the
teamwork function is unavailable.
If Teamwork function and Teamwork parameter
synchronization are both set to Enable, you can
select Set Local or Set Teamwork when setting
parameters.
NOTE
● Set Local: Set parameters for the local unit.
● Set Teamwork: Set parameters for all units in a
teamwork group.
Specifies the total number of units in this group. The
value is an integer ranging from 1 to 32.
NOTE
This parameter is displayed after Teamwork function is set
to Enable.
Specifies the number of running units in this group.
The value is an integer ranging from 1 to the value
of Number of systems in this group.
NOTE
This parameter is displayed after Teamwork function is set
to Enable.
Copyright © Huawei Technologies Co., Ltd.
4 Power-On Commissioning
104