Figure 3-56 Connecting the pressure tubes
Step 3 Connect the differential pressure sensor cables to terminals 4, 5, and 6 of X502.
----End

3.6.10.2 (Optional) Installing a Downflow Differential Pressure Sensor

Prerequisites
Context
Procedure
Step 1 Secure the differential pressure sensor inside the cabinet using two M3 screws,
with the pressure inlet tube port facing downwards.
Issue 07 (2021-12-30)
The PU hoses for connecting the differential pressure sensor are ready.
The hoses and cables are bound along the routes.
The pressure tube at the air return side needs to be bound to the top cabinet
beam horizontally. If a blocked damper is configured, route the pressure tube
through the hole reserved in the damper enclosure frame, and bind the
pressure tube to the cable bridge inside the damper enclosure frame.
After powering on the NetCol8000, choose Settings > System Settings >
Common Settings, and set Air-side difference pressure sensor type to
0~500Pa.