Huawei NetCol8000-C070 User Manual page 121

In-room chilled water smart cooling product
Hide thumbs Also See for NetCol8000-C070:
Table of Contents

Advertisement

NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Procedure
Step 1 On the home screen, choose Settings > Comm Settings > WAN IP Settings, and
set the IP address, subnet mask, and gateway based on the actual plan.
Figure 4-8 WAN IP Settings
Step 2 On the home screen, choose Settings > Comm Settings > Modbus Settings and
set Link mode to Server and client or Client. Set Client encryption to Enable.
Figure 4-9 Modbus Settings
Step 3 Enter the actual IP address of the NMS.
Step 4 When Client encryption is set to Enable, set NMS port number to 32907. When
Client encryption is set to Disable, set NMS port number to 32906.
Issue 07 (2021-12-30)
NO TE
The WAN IP address cannot be in the 192.168.X.X network segment.
NO TE
The encryption mode must be the same as it on the NMS.
Copyright © Huawei Technologies Co., Ltd.
4 Power-On Commissioning
111