Huawei NetCol8000-C070 User Manual page 123

In-room chilled water smart cooling product
Hide thumbs Also See for NetCol8000-C070:
Table of Contents

Advertisement

NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Figure 4-10 Setting SNMP communications parameters
Step 2 Set SNMP Version based on site requirements, and then tap Submit.
Step 3 Set Read Community and Write Community.
1.
2.
Step 4 Add an SNMPv3 user.
1.
2.
Issue 07 (2021-12-30)
When SNMP Version is set to ALL or SNMPv1&v2c, you can set Read
Community and Write Community by referring to
When SNMP Version is set to ALL or SNMPv3, you can add an SNMPv3 user
by referring to
Step
4.
Tap the text box next to Read Community, set the read community
parameter based on the actual plan, tap
Tap the text box next to Write Community, set the write community
parameter based on the actual plan, tap
Tap Add under SNMP V3.
Set User Name, Auth Protocol, and Prop Protocol based on the actual plan.
MD5 and DES protocols are not secure. It is recommended that you set Auth
Protocol to SHA2-512, and set Prop Protocol to AES-256. The following
operations use the recommended settings as an example.
Figure 4-11 Setting the protocol type
Copyright © Huawei Technologies Co., Ltd.
4 Power-On Commissioning
Step
3.
, and tap Submit.
, and tap Submit.
113