4.5.4 Setting Communications Parameters

4.5.4.1 Setting Access Control Parameters

Path: Settings > Comm Settings > Access Control
Figure 4-6 Access Control
Parameter
Remote control
SSH (LAN)
Issue 07 (2021-12-30)
Check whether the number of standby devices on the topology is the same as
the actual device number.
If yes, go to 4.
If no, check the cable connection and the settings of teamwork control
parameters.
Check whether the number of online devices on the topology is the same as
the actual device number.
If yes, the check is complete.
If no, check the cable connection and the settings of teamwork control
parameters.
Copyright © Huawei Technologies Co., Ltd.
Description
● Enable: Users can control the unit over their
monitoring system.
● Disable: Users cannot control the unit over their
monitoring system.
● Enable: Access to the unit through the intranet using
SSH (default port number: 22) is allowed.
● Disable: Access to the unit through the intranet
using SSH is not allowed.
● If this parameter is set to Disable, the function will
be enabled within 30 minutes after power-on by
default.
● If this parameter is set to Enable, the function will
be automatically disabled after 24 hours of running.
4 Power-On Commissioning