Installation Preparations; Tools - Huawei NetCol8000-C070 User Manual

In-room chilled water smart cooling product
Hide thumbs Also See for NetCol8000-C070:
Table of Contents

Advertisement

NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Table 3-1 Pipe ports
Item
Water outlet pipe
Water inlet pipe
Humidifier water inlet pipe
Drainpipe
Installation Requirements
Table 3-2 Installation requirements
Item
Door
Floor
Pipe routing
Maintenance distance
Power distribution
requirements

3.2 Installation Preparations

3.2.1 Tools

Table
NetCol8000-C. Add or delete tools as required.
Issue 07 (2021-12-30)
3-3,
Table
3-4,
Table 3-5
Copyright © Huawei Technologies Co., Ltd.
Specifications
G 2 inch port with internal threads
G 2 inch port with internal threads
G 3/4 inch port with external threads
G 3/4 inch port with internal threads
Specifications
Width ≥ 1.7 m; height ≥ 2.3 m; turning radius ≥
3.2 m
Floor bearing capacity ≥ 400 kg/m
Upflow: left pipe routing, left and bottom pipe
routing
Downflow: left and bottom pipe routing
Front maintenance distance ≥ 900 mm
Leakage circuit breakers are not recommended
for the main power route. If leakage circuit
breakers are required by the customer or by
local regulations, use the residual current
circuit breaker (RCCB) that is not sensitive to
the single-phase DC pulses and transient
current pulses.
and
Table 3-6
list the tools for installing the
3 Installation
2
35