NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Exercise caution because the device is still energized after it is shut down on the
screen of the display module.
Step 2 Open the front door and turn off the general switch. For a device that has two
power inputs, turn off the active power switch QF1 and standby power switch
QF2.
Step 3 Remove the fan maintenance baffle plate.
Figure 6-18 Removing the fan maintenance baffle plate
Step 4 After the electric heater cools to the room temperature, cut off the cable tie on
the electric heater cable and disconnect the interconnection terminal.
Step 5 Remove the four bolts from both ends of the electric heater and take out the
electric heater.
Figure 6-19 Removing an electric heater
Step 6 Install and secure the new electric heater by performing
the fan maintenance baffle plate and close the front door.
Step 7 On the home screen, choose Maint > Wizard Startup, and commissioning the
electric heater to check that the heater is normal. Then exit from the wizard
startup mode.
Issue 07 (2021-12-30)
NO TICE
Copyright © Huawei Technologies Co., Ltd.
6 Maintenance
Step 6
to
Step
3. Install
175