Downflow - Huawei NetCol8000-C070 User Manual

In-room chilled water smart cooling product
Hide thumbs Also See for NetCol8000-C070:
Table of Contents

Advertisement

NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Step 5 Paste the thermal insulation foam on the pipe and install the cover plate for the
left side knock-out hole.
----End

3.5.2.2 Downflow

Context
Tools: 75# open-end wrench, 36# open-end wrench, 18# pipe wrench, sealant
(used for pasting thermal insulation foam), screw thread sealant.
Procedure
Step 1 Remove the baffle plate at the bottom of the cabinet, and knock off the U-shaped
hole in the baffle plate, as shown by (1) in
● Connect pipes and then wrap thermal insulation foam around the whole
pipeline.
● Based on the hardening property of yellow adhesive, inject water and preserve
the pressure at least 8 hours after an adapter is connected.
Step 2 To avoid deforming the pipe, use a 75# open-end wrench to fix the pipe nut, use a
36# open-end wrench to fix the plug, and then remove the plug, as shown by (2)
in
Figure
Step 3 Apply thread sealant evenly on the joints of external screw threads, and install the
pipes from inside out, as shown by (3) in
Step 4 Use a 75# open-end wrench and 18# pipe wrench to fix the pipe, as shown by (4)
in
Figure
Step 5 Install the pipe baffle plate at the bottom of the cabinet, and wrap the pipe with
thermal insulation foam, as shown by (5) in
Issue 07 (2021-12-30)
NO TICE
3-25.
3-25.
Copyright © Huawei Technologies Co., Ltd.
Figure
3-25.
Figure
3-25.
Figure
3-25.
3 Installation
55