NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Locati
on
● The default addresses of T/H sensors purchased from Huawei are 1.
● After the addresses are set, power on the device, choose Settings > System
Settings > T/H sensor on the home screen of the display module, and set the
sensors in the aisles corresponding to the addresses to Enable. Otherwise, the
sensors will not work.
----End
3.6.9 (Optional) Installing the Direct Free-cooling Plenum
After powering on the NetCol8000, choose Settings > System Settings > Indoor
Fan, and set Direct free-cooling to Enable.
For details about how to install the direct free-cooling plenum, see the documents
delivered with it.
3.6.10 (Optional) Installing a Differential Pressure Sensor
Bind the pressure inlet tube along the pipeline, and the distance between two
binding points should not exceed 2.5 m.
3.6.10.1 (Optional) Installing an Upflow Differential Pressure Sensor
Prerequisites
●
●
Issue 07 (2021-12-30)
Display
Addr
Name
ess
Temper
27
ature
and
humidit
y at the
return
air
valve
NO TICE
NO TICE
Install either the differential pressure sensor or the cap. If the cap is installed,
skip this section.
The hoses and cables are bound along the routes.
Copyright © Huawei Technologies Co., Ltd.
DIP Switch No.
1
2
3
ON
ON
OFF
3 Installation
4
5
6
ON
ON
OFF
79