Huawei NetCol8000-C070 User Manual page 151

In-room chilled water smart cooling product
Hide thumbs Also See for NetCol8000-C070:
Table of Contents

Advertisement

NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Alarm ID
Alarm Name
A007-01
Return air 1 temp/
humid sensor comm
failed
Return air 2 temp/
humid sensor comm
failed
Return air 3 temp/
humid sensor comm
failed
Return air damper 1
temp/humid sensor
comm failed
Cold aisle 1 temp/
humid sensor comm
failed
Cold aisle 2 temp/
humid sensor comm
failed
Cold aisle 3 temp/
humid sensor comm
failed
Cold aisle 4 temp/
humid sensor comm
failed
Cold aisle 5 temp/
humid sensor comm
failed
Hot aisle 1 temp/
humid sensor comm
failed
Hot aisle 2 temp/
humid sensor comm
failed
Hot aisle 3 temp/
humid sensor comm
failed
Hot aisle 4 temp/
humid sensor comm
failed
Hot aisle 5 temp/
humid sensor comm
failed
Fresh air 1 temp/
humid sensor comm
failed
Issue 07 (2021-12-30)
Alarm
Severity
Major
Copyright © Huawei Technologies Co., Ltd.
Possible Cause
● The cables to the
temperature and
humidity sensor are
loose or damaged.
● The DIP switch of
the temperature
and humidity
sensor is set
incorrectly.
● The temperature
and humidity
sensor is faulty.
● The
communications
port of the main
control board is
faulty.
6 Maintenance
Solution
1. Check the cables to
the temperature
and humidity
sensor.
2. Set the DIP switch
of the temperature
and humidity
sensor correctly.
3. Maintain or replace
the temperature
and humidity
sensor.
4. Maintain or replace
the main control
board.