Procedure
Step 1 Loosen the left knocking-off padding cover of the cabinet using a Phillips
screwdriver. Take out the cover and remove the knocking-off padding.
Figure 3-23 Removing the knocking-off padding cover
Step 2 Remove the pipe plug using a 75# open-end wrench and 36# open-end wrench
(the 75# open-end wrench is used to secure the pipe nut and the 36# open-end
wrench is used to secure the plug to prevent the pipes from being distorted), as
shown by (1) in
Step 3 Apply thread sealant to the joints of the outer screw threads of the external pipe,
as shown by (2) in
Step 4 Connect the water pipe by using a 75# open-end wrench and an 18# pipe wrench,
as shown by (3) in
Figure 3-24 Connecting pipes
Issue 07 (2021-12-30)
Figure
3-24.
Figure
Figure
NO TE
The figure uses side pipe routing as an example. If bottom pipe routing is used, purchase
right angle elbows with DN50 outer threads onsite.